{"ok":true,"generatedAt":"2026-11-27","cluster":{"slug":"10240","rank":"03","name":"万卡智算集群","englishName":"10,240-GPU AI GIGAFACTORY","gpuCount":10240,"subtitle":"标准 10,240× H200 / 144× GB200 NVL72 超级智算中心 · 1,280 节点 × 8 卡 / 10 个 SU 集群岛","summary":"四个数据大厅、十个千卡 SU 集群岛与三级 Clos 核心光交换平面，承载万亿参数 MoE 持续预训练；故障自治、电力调度与光链路遥测是同等重要的一等系统。","defaultPlatform":"h200-141g","suCount":10,"dataHalls":4,"floorDimensionsM":"4 Halls × 62 × 42 m（独立防火分区）","racks":{"compute":320,"networkStorage":32,"cdu":32,"total":384},"network":{"architecture":"3-Tier Clos Spine-Leaf + Core Optical Spine","leaf":320,"spine":160,"core":80,"ratio":"SU 内 1:1；跨岛按业务拓扑隔离","optics":32768,"opticType":"OSFP 400G/800G","fiberCores":98304,"trunkKm":560,"description":"320 Leaf + 160 Spine + 80 Core Quantum-2/X800，32,768+ OSFP 光模块与 560+ 公里主干光纤；Core Optical Spine 连接四厅十岛。"},"power":{"itMw":16.4,"facilityMw":18.8,"rackKw":52,"pue":1.14,"grid":"110kV 专用变电站（双主变）","backup":"12×2.5MW 高压柴发阵列","annualElectricityCny":131712000},"cooling":{"type":"DLC + 蒸发冷却塔群","primarySupplyC":28,"secondarySupplyC":32,"secondaryReturnC":42,"cdu":32,"description":"四厅独立二次侧环路，32 台 CDU/Manifold 柜，蒸发冷却塔群与余热回收接口。"},"storage":{"capacityPb":36,"bandwidthGBs":4500,"type":"All-NVMe DeepSeek 3FS / Lustre","checkpoint":"4.5 TB/s Checkpoint 聚合写入"},"compute":{"fp8Pflops":20265,"vramPbH200":1.44,"training":"万亿参数 MoE / 多租户千卡预训练"},"economics":{"capexCny":2650000000,"capexLabel":"约 ¥26.5 亿（H200 标准版）","alternateCapexLabel":"GB200 NVL72 按 144 柜与独立电力增容核价"},"operations":{"mtbf":"日均 2.8 次 GPU/光模块/NVLink 硬件降级事件（生产目标口径）","incidentsPerDay":2.8,"recovery":"自动隔离 + 异步 Checkpoint 恢复 < 90 秒","mfu":"万卡线性扩展目标 ≥82%；按模型/通信域实测验收"},"capexBom":[["HGX H200 计算节点","1,280 节点 × 8 GPU",2080000000,"十个千卡 SU，批量一致性固件与老化"],["三级 Clos 光网络","320 Leaf + 160 Spine + 80 Core",230000000,"32,768+ 光模块、560km 主干光纤"],["全闪并行存储","36PB / 4.5TB/s",100000000,"3FS/Lustre，独立元数据与故障域"],["液冷与冷塔群","32 CDU + 四厅环路",90000000,"蒸发冷却塔、Manifold 与水质控制"],["110kV 电力与柴发","专用变电站 / 12×2.5MW",70000000,"双主变、高压并机、母线与 UPS"],["四数据大厅工程","384 Racks / 独立消防",50000000,"承重、桥架、封闭通道与动环"],["软件与故障自治","调度 / 遥测 / 自动恢复",30000000,"拓扑感知调度、Checkpoint 与数字孪生"]],"playbook":["千卡岛作为最大默认训练域；跨岛作业需要显式审批，避免跨 Core 拥塞影响其他租户。","XID、NVLink 降级和光模块高 BER 事件触发自动摘除；备用节点热替换后 <90 秒从异步 Checkpoint 恢复。","按 GPU、Rail、Leaf、Spine、Core 五级遥测定位抖动，任何恢复动作均写入不可变事件时间线。","每厅独立做电力、漏液与消防演练；柴发按月带载，主变/冷塔按 N+1 失效场景复核。"]}}